| Shape/Structure | Enclosed Limit switches |
|---|---|
| Service life | General type |
| Actuator | Plunger |
| Frequency | 50/60 Hz |
| Contact form | SPDT |
| Load | Micro load |
| Ratings (AC): Non-Inductive load | Rated voltage: 125 VAC / Resistive load: 0.1 A(NC) 0.1 A(NO) |
| Ratings (DC): Non-Inductive load | Rated voltage: 8 VDC / Resistive load: 0.1 A(NC) 0.1 A(NO) Rated voltage: 14 VDC / Resistive load: 0.1 A(NC) 0.1 A(NO) Rated voltage: 30 VDC / Resistive load: 0.1 A(NC) 0.1 A(NO) |
| Protective circuit | Classification of protection against electric shock: Class II (Grounding not required with double) insulation Short-circuit protective device: 10 A fuse type gI or gG (IEC60269) |
| Ambient temperature | Operating: -10 to 80 ℃ (no icing) |
| Ambient humidity | Operating: 35 to 95% RH (no condensation) |
| Permissible operating frequency (Mechanically) | 120 operations / 1 minute max. |
|---|---|
| Permissible operating frequency (Electrically) | 30 operations / 1 minute max. |
| Contact resistance (Initial value) | 15 mΩ max. |
| Insulation resistance | 100 MΩ min. (at 500 VDC) |
| Dielectric strength | Between each terminal of the same polarities: 1,000 VAC 50/60 Hz for 1 min Between each terminal and non-live-metallic part: 2,000 VAC 50/60 Hz for 1 min |
| Impulse withstand voltage | Between each terminal and non-live-metallic part: 2.5 kV |
| Durability (Mechanically) | 10,000,000 operations min. (Temperature, Humidity conditions: 5 to 35 ℃, 40 to 70% RH) |
| Durability (Electrically) | 500,000 operations min. (Temperature, Humidity conditions: 5 to 35 ℃, 40 to 70% RH) |
| Vibration resistance (Malfunction) | 10 to 55 Hz, 1.5-mm double amplitude |
| Shock resistance (Destruction) | 1000 m/s**2 max. |
| Shock resistance (Malfunction) | 300 m/s**2 max. |
| Pollution degree | 3 (EN60947-5-1) |
| Degree of protection | IP67 |